23 Results for the search "current":
Author: h.gras
Type: Model
Downloaded: 187 times
Date: 2020-04-10
Display short-circuit date on buses
Description:
This folder contains scripts which automatically find the short-circuit impedances and currents at all buses with visible names.
These information are displayed in the GUI
Tag(s): short-circuit, impedance, thevenin
Author: h.gras
Type: Model
Downloaded: 428 times
Date: 2018-06-08
Vacuum Circuit breaker (VCB)
Description:
Three main characteristics of VCBs have been taken into account in the implemented model:
1. the chopping current value;
2. the cold withstand voltage characteristic (or cold gap breakdown v... see moreoltage);
3. the high frequency current quenching capability.
Ref: Transient Recovery Voltages in Vacuum Circuit Breakers Generated by the Interruption of Inrush Currents of Large Motors
A. Borghetti, F. Napolitano, C.A. Nucci, M. Paolone, M. Sultan, N. Tripaldi
Tag(s): Vacuum, circuit breaker, VCB,
Author: thpapad
Type: Document
Downloaded: 343 times
Date: 2017-11-03
INDUCED VOLTAGES AND CURRENTS: OVERVIEW AND EVALUATION OF SIMULATION MODELS AND METHODOLOGIES
Description:
In this paper induced voltages and currents caused by underground cables are calculated in cable sheaths and nearby metallic pipelines. The performance of several simulation methods and models are inv... see moreestigated in steady-state, considering also different implementations in ATP-EMTP, EMTP-RV and PSCAD/EMTDC. The analysis is extended in the simulation of transient overvoltages in cable systems, evaluating the accuracy of two widely used simulation models. The influence of different parameters is investigated, among them specifically the earth properties. Results reveal that implementing accurate earth representations, earth conduction effects have a significant impact on induced voltages at the power frequency, while for high frequency phenomena the influence is minor.
Tag(s): induced voltages
Author: n.sene
Type: Publication
Date: 2015-10-22
Fault Current Limiters in Industrial Power Systems
Description:
The concept of saturable core fault current limiter (FCL) is relatively known nowadays. It usually consists of two reversely magnetized cores per phase to effectively limit the fault current passively... see more and immediately upon its inception. In this paper prospects of application of fault current limiters in industrial power systems will be considered. Industrial power systems (distribution networks) are widespread and include a number of various electrical appliances. The power systems development (addition of new power plants, interconnections, etc.) may lead to more intense short circuit currents at the fault location. Furthermore, industrial systems may possess on-site generation which can increase fault current levels as well. All these factors might require appropriate upgrades of industrial system electrical equipment (especially switchgear) or special operating procedures (for instance avoiding parallel operation). Another alternative is the installation of fault current limiters. In this light, a series of simulations were carried out in order to observe the impact of fault current limiters on short circuit currents in an industrial power system using the EMTP-RV software program.
Keywords: saturable core fault current limiter (FCL), industrial power system, induction machine, EMTP; fault current analysis, medium voltage
Tag(s): saturable core fault current limiter (FCL), industrial power system, induction machine, EMTP; fault current analysis, medium voltage
Author: n.sene
Type: Publication
Date: 2015-04-01
Correlation of lightning events and faults in distribution power networks
Description:
The paper deals with the analysis of the possible correlation between cloud-to-ground lightning discharges and relay operations inferred by using the experimental data obtained means of a measurement ... see moreset-up, installed on an Italian MV distribution network, and a statistical procedure based on the coordinated use of the Italian Lightning Location System (LLS) CESI-SIRF, the monitoring systems of protection manoeuvres and an advanced simulation tool for the calculation of lightning induced overvoltages. The procedure takes into account the uncertainties related to the estimation of lightning stroke location and current amplitude provided by the LLS. The experimental set-up, composed by a distributed monitoring system, is able to measure a-periodic voltage transients characterized by a frequency content up to 4 MHz. Three of these units have been installed in the feeder of a three-phase overhead distribution network with a total length of 21 km. The same feeder is protected with overcurrent and zero-sequence relays whose operations are recorded by a monitoring system with a 10-ms sampling time. The data collected during one year of operation of the experimental set-up have been analyzed together with the data collected by the LLS for a 144 km2 area covering the equipped feeder and its surrounding area, in order to account for all direct and indirect lightning events that may have caused a relay intervention. The data have been also used to test the calculation model. The paper eventually reports the results of the correlation analysis carried out using the mentioned procedure, which is used to evaluate the probability that a specific event, detected by the LLS and time-correlated to relay operation, may have been the cause of a flashover in the network.
Authors: A. Borghetti, F. Napolitano, C.A. Nucci, M. Paolone, M. Bernardi, F. Rachidi, K. Yamabuki
CIGRE 2008 - a joint research project
Tag(s): Lightning protection, lightning-to-fault correlation, lightning location systems, lightning performance of distribution lines, induced overvoltages, a-periodic voltage transient measurement, EMTP.