Real Case of a Resonance in a Power Plant

Overvoltages were identified on the MV and LV networks of a Hydro Power Plant as the cause of the trip of the LV maximum voltage protection, compromising the normal operation of the system. Following this event, measurements were conducted and the presence of a very high 23rd harmonic, potentially responsible for the various overvoltages, was identified associated to the operation of the Plant’s Synchronous Machine Frequency Control System (FCS). It was concluded then that this harmonic would
Author(s): Andreia Leiria
Type: EMTP User Conference 2021
Downloaded: 0
Date: 2021-09-02
Rating: * 0 vote(s)
Tag(s): harmonics, power uality, resonance