Transient enclosure voltage (TEV) also known as Transient ground potential rise (TGPR) is a special case of VFTO. This phenomenon refers to short rise time, short duration high voltage transient which appear on earthed enclosure of GIS. This is mainly through the coupling of internal transients on conductor refracted to the enclosure at enclosure discontinuities such as air terminations, insulated flanges at GIS/Cable interfaces and some current transformers. Primarily disconnector switch operat
Author(s): N.K. Nathan
Type: EMTP User Conference 2021
Downloaded: 0
Date: 2021-09-01
Rating: * 0 vote(s)
Tag(s): gis, vfto, very fast transient