Dynamic Exponential Load

EMTP Software Icon

version 1.0.1 (22.8 KB) by h.gras


This device is an implementation of the three-phase exponential load model. The load active power and reactive power vary as function of its voltage amplitude and frequency. This device is implemented as described in [1]. It allows to perform classical and sophisticated dynamic-stability studies in EMTP. This device can be used in the load flow and time-domain simulations.

During the load initialization, the initial active power and initial reactive power are used to find the load-flow. The load voltage magnitude and phase with update from the load flow results automatically.
[1] "Load representation for dynamic performance analysis (of power systems)," IEEE Transactions on Power Systems, vol. 8, no. 2, pp. 472-482, May 1993.

Rating:

* 1 vote(s)

Downloaded: 76 times

Date: 2022-10-20

Do you like the contribution? Rate it!
X