CB_arc_CM

EMTP Software Icon

version 1.0.1 (22.8 KB) by AdminEMTP-RV


This is an interesting case of the study of arc-circuit interaction in case of the interruption of a short-line fault.The arc is represented by a composite Cassie-Mayr model and the line is represented as frequency-dependant.
The case shows the application of black-box arc modeling in the study of kilometric-line fault capability of a 420 kV circuit-breaker. By zooming on the arc current and voltage near current-zero, post-arc current and initial TRV may be visualized in both cases of clearing and thermal failure.