ZnO Arrester Models

Submitted by Anonymous (not verified) on Wed, 05/18/2011 - 15:34

After generating ZnO surge arrester using Zno Data Function we obtain a punch card which we can use for any surge arrester from a particular model and manufacturer for any rated voltage.

What value of Vref do we need to enter in order to scale the data?

For example - I produced a 96kV rated surge arrester .pun card - then wanted to convert it to a 120kV rated equivalent. The Zno Data Functionrecommends we use 2 x Vrated when generating the data - ie 192kV. In the ZnO model for the 120kV rated equivalent should I make Vref = 240kV ?

Why can't I make Vref = Vrated to simplify things?

Any help would be appreciated.

AdminEMTP-RV

For numerical stability purposes only, the program suggests that you use 2 x V rated. But other values function also in most cases

To convert an already functionnal arrester model, you only need to multiply the Vref value by a proportion. For your exampe this proportion in your case is 120/96.

Wed, 05/18/2011 - 15:35 Permalink
saulo.hernandez

Someone could help me to modelling ZnO surge arrester?

Details are as follows:
- SIEMENS
- Duty cycle voltage: 96 kV
- MCOV: 76 kV
- TOV capability: 109 kV (for 1 s) and 102 kV (for 10 s)
- Protective level (Maximum discharge voltage):
   * FOW 10 kA:259 kV
   * for 8/20 us (impulse):
     - at 1.5  kA: 202 kV
     - at 3.0  kA: 214 kV
     - at 5.0  kA: 221 kV
     - at 10.0 kA: 235 kV
     - at 15.0 kA: 252 kV
     - at 20.0 kA: 263 kV
     - at 40.0 kA: 294 kV
   * for 45/90 us (impulse):
     - at 500  A: 188 kV
     - at 1.0  kA: 195 kV
     - at 2.0  kA: 204 kV

Appreciate your help,
 

Saulo Hernandez

Mon, 03/10/2014 - 04:47 Permalink