4 Results for the search "TRV":
Electrical Transients in Power Systems Example in EMTP
Description:
RL and RLC circuit, and the simple TRV example from Chapter 3 of the textbook 'Electrical Transients in Power Systems' by Allan Greenwood - modeled in EMTP.
Tag(s): trv, simple, rlc, greenwood, allan greenwood, electrical transients
Content of the webinar studies from A to Z on TRV
Description:
Designs built or presented during the webinar of the series Studies from A to Z on Transient Recovery Voltage
Models built:
- Rating TRV envelop (IEC 62271-100 / C37.010 - 2011)
- CP / ... see moreFD lines
- Thevenin equivalent of a network
Tag(s): TRV, Transient recovery voltage, short-line fault, terminal fault, substation, 62271, 37.011, lines, switching, thevenin
Transient recovery voltages in vacuum circuit breakers generated by the early-interruption of the inrush current of large motors
Description:
The switching of medium voltage electrical motors is typically realized by means of vacuum circuit breakers (VCBs) essentially in view of their elevated number of switching cycles. As known, switching... see more of VCBs generates important transient recovery voltages (TRVs)
that need to be properly evaluated in both VCB sizing and in the power system insulation coordination. As large medium voltage electrical motors are installed into plants typically controlled by means of Supervisory Control And Data Acquisition (SCADA) systems,
maneuvers that involve the motor inrush followed by its sudden de-energization (due, in general, to the intervention of an automatic diagnostic function), resulting into important TRVs, are not unusual. The paper aims at investigating the TRVs due to this specific type of
VCB switching by means of a model implemented in the EMTP-RV simulation environment. By making reference to a real plant, the validation of the implemented models is obtained by comparing the simulation results with some experimental transients provided by the plant data fault recorder. The paper finally discusses the adequacy of different countermeasures by analyzing their effectiveness for the TRVs limitation.
Authors: A. Borghetti, F. Napolitano, C.A. Nucci, M. Paolone, M. Sultan, N. Tripaldi
CIGRE - International Symposium “Assessing and Improving Power System Security, Reliability and Performance in Light of Changing Energy Sources” Recife, Pernambuco, Brazil, April 3-6, 2011
Topic 3 – System technical performance
Subtopic 3.5 – Switching and lightning transient on power systems. Impact on performance and measurements
Tag(s): Transient recovery voltages, vacuum circuit breakers, motor inrush currents, EMTP simulations
CB_arc_CM
Description:
This is an interesting case of the study of arc-circuit interaction in case of the interruption of a short-line fault.The arc is represented by a composite Cassie-Mayr model and the line is represente... see mored as frequency-dependant.
The case shows the application of black-box arc modeling in the study of kilometric-line fault capability of a 420 kV circuit-breaker. By zooming on the arc current and voltage near current-zero, post-arc current and initial TRV may be visualized in both cases of clearing and thermal failure.
Tag(s): Example, Protection